Code
Description
996
No connection to Fronius
Solar.web
997
Deviation between invert-
ers
998
Fronius Solar.net loop is
open more than 24h
999
24h no feed in
1000* -
Service-Message
1001*
1201* -
Service-Message
1210*
* ... Code appears only with Eventlogging and in the Error Counter
Customer service
IMPORTANT! Contact your Fronius dealer or a Fronius-trained service technician if
-
-
Operation in
When operating the inverter in extremely dusty environments:
dusty environ-
when necessary, clean the cooling elements and fan on the back of the inverter as well as
ments
the air intakes at the mounting bracket using clean compressed air.
Behaviour
No connection to Fronius So-
lar.web
Deviation of the kWh value be-
tween inverters depending on
the settings in Fronius So-
lar.web
Fronius Solar.net is not closed
and the X-LED is red on the
Datamanager or Datalogger
1. No communication between
inverter and Datamanager or
Datalogger more than 24h
2. No communication between
Fronius Sensor Card and Da-
tamanager or Datalogger more
than 2h
Are harmless for a faultless
feeding in process and gives
information about the internal
processor status
Are harmless for a faultless
feeding in process and gives
information about the internal
processor status
an error appears frequently or all the time
an error appears that is not listed in the tables
Remedy
1. Check LED status on Data-
logger
2. Restart Datalogger
3. Check internet connection
4. Check if customer has got
timer to switch off internet con-
nection and time interval set-
tings is too short
Check settings in system ad-
ministration in Fronius So-
lar.web (real Wpeak per
inverter and deviation), inquire
if there are shadows etc.
1. Check Fronius Solar.net
loop
2. Check networ cabling
3. Check Fronius Com Card
1. Check LED status from Da-
tamanager or Datalogger
2. Check archive values and
Fronius Solar.net loop
119