Herunterladen Inhalt Inhalt Diese Seite drucken

Fronius Symo 10.0-3-M Serviceanleitung, Ersatzteilliste Seite 163

Netzgekoppelter wechselrichterfronius
Vorschau ausblenden Andere Handbücher für Fronius Symo 10.0-3-M:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

(3)
(3)
(2)
(1)
CAUTION!
The PCM paste must not be damaged or
removed when inserting the SymoPS DC
Insert the new SymoPS DC and positi-
2
on accordingly
NOTE!
To avoid applying mechanical stress to
the solar modules, apply the torque in
the same sequence
Fit the SymoPS DC solar modules with
3
four 4x9 TX20 screws (3). Observe the
torque sequence to avoid applying me-
chanical stress
First pretension all four screws to [0.5
Nm] and then tighten them to [2 Nm]
Thread in and connect all cables and
4
plug connections (1)
Fit the SymoPS DC with 13/15 4x9
5
TX20 screws (2)
[2 Nm]
NOTE!
Ensure that the ferrite cores and their
holders are fitted correctly
Close the inverter and place it in the
6
wall bracket (see "Opening and closing
the device" and necessary „Replacing
(1)
the Overvoltage PC board" sections)
Switch on the inverter and then carry out a
fan test via the display (see operating inst-
ructions)