Herunterladen Inhalt Inhalt Diese Seite drucken

Maico PPB 30 K Montageanleitung Seite 45

Endmontage-set für pushpull lüftungssysteme
Vorschau ausblenden Andere Handbücher für PPB 30 K:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

LEDs
LED flashing modes:
Parameter
Set value /
ventilation level
Sensors
0
1
2
3
4
5
6
7
ModBus
1
settings
2
3
ModBus
1
address
2
3
4
5
6
7
LED flashing rapidly
10 Commissioning | UK
Setting /
description
No sensor
1 internal sensor
1 internal sensor + 1 external sensor
1 internal sensor + 2 external sensors
1 internal sensor + 3 external sensors
0 internal sensors + 1 external sensor
0 internal sensors + 2 external sen-
sors
0 internal sensors + 3 external sen-
sors
Select how many internal and external
sensors are connected/combined. The
PP 45 HYI internal sensor and the
PP 45 HY, PP45 CO2 and PP 45 VOC
external sensors are available.
RS-485 inactive
ModBus active 9600 baud
ModBus active 19200 baud
This adjuster activates ModBus and
sets the baud rate.
Notice: When the Modbus interface
is active, external sensors/LTs/RLS
cannot be connected.
Address 10
Address 11
Address 12
Address 13
Address 14
Address 15
Address 16
The ModBus address
is selected with this adjuster.
LED flashing slowly
45

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Rls 45 oRls 45 kPpb 30 rcPpb 30 o