Configuration level
Display
Function
3 SetFunction
Determines the function of the digital
In 2
input „In 2"
Submenu for setting the digital
Digital Output
outputs
K1 Switch
Defi nes the type of output
K1 Fn
Determines the function of output K1
K2 Switch
Defi nes the type of output
K2 Fn
Determines the function of output K2
Determines the delay time between
Error Time
error recognition and error message
Determines the function of the
ErrorAction
process valve if there is an error
message
Switches ON/OFF valve travel
TravelTErrFn
monitoring
Maximum position deviation of the
TravelLevel
valve
TravelTime
Valve travel time monitoring
Switch point that switches after K1 is
AlarmMaxK1
exceeded
Switch point that switches after K1 is
AlarmMinK1
undershot
Switch point that switches after K2 is
AlarmMaxK2
exceeded
Switch ponit that switches after K2 is
AlarmMinK2
undershot
Preferred direction when both signal
PrefDir
inputs are connected
PwrFailDir
Function during power failture
Copies parameters to various working
CpyParaSet
memories (P1/P2/P3/P4)
SideStep
®
Industrial
Value range
Factory setting
OFF/ON
OFF
Safe/ON
ParmSetB0
ParmSetB1
NC / NO
NO
P min
no
P max
P min/max
Active
Error
Warning
NC / NO
NO
P min
No
P max
P min/max
Active
Error
Warning
0.0...100.0 s
0.2s
Close/Open/Hold Close
OFF / ON
ON
0.0...100.0%
1.0%
0.0...120.0s
10.0s
0.2...99.8%
10.0%
0.2...99.8%
90.0%
0.2...99.8%
10.0%
0.2...99.8%
90.0%
Close/Open/
Close
Hold
Close/Open/Hold Close
24 / 28
Configuration level Display
Function
Valve position at actual value output
4 SetCalibration
OutMinPos
signal 0/4mA
Valve position at actual value output
OutMaxPos
signal 20mA
Scaling
Switching on the scaled display
Decimal-
Determines the decimal points
point
displayed
Defi nes the display which corresponds
≙
4mA
to a 0/4mA signal
Defi nes the display which corresponds
≙
20mA
to a 20mA signal
IR-Port
Not available
Submenu for setting the fi eldbus
Fieldbus
address if available
Submenu for setting the communica-
WebServer
tion settings
Defi nes the communication connec-
ComPort
tion
State
Displays the actual connection state
BT Name
The bluetooth name can be entered
The PIN code of a bluetooth connec-
PinCode
tioncan be entered
Value range
Factory setting
0...100%
0.0%
0...100%
100.0%
ON / OFF
OFF
0...2
1
0%
100%
OFF
OFF
OFF
OFF
Auto
Auto
Serial
Analog
PC/BT
PDA/BT
Phone/BT
SideStep
0000...9999
0000
SideStep
®
Industrial
25 / 28