Switch point
Operating
direction
Return to
en
measuring mode
PHX20 and
PHX21
16
Please note: if the "HILO" message is inactive, the error "Er06" is dis-
played if the display range (-1999...+9999) is overshot.
Both functions are not available at Cerabar T
By pressing the A or B key 1-8 times depending on the menu item
selected.
6
Technical data
•
Display: 4-digit, red LED display
•
Digit height: 7.62 mm; programmable decimal point setting
•
Display range: -1999...9999
•
Accuracy: 0.2% of the span ±1 digit
•
Electrical connection: at transmitter with 4...20 mA output and
elbow plug DIN 43 650, reverse-polarity proof
•
Display power supply: not required, own supply from current loop
•
Voltage drop: ≤ 5 V (corresponds to load: max. 250 Ω)
•
Conversion rate: 3 measurements per second
•
Damping: 0.3...20 s (can be adjusted)
•
Back-up: non-volatile EEPROM