Trio
Removing/fitting front cover
WARNING Chapter 10.1
!
1. On decentralised units, remove the hood
(4 screws, no Fig.).
2. Remove the 14 screws on front cover and
take off front cover.
3. To fit the front cover, proceed in reverse
order. Ensure that the cover is seated cor-
rectly and no false air can be drawn in.
10.3 Fitting wall bracket
310/410
320/470
NOTICE
Only install the ventilation unit on a wall with
sufficient load-bearing capacity (at least
200 kg/m³).
Before installing on the wall, have cus-
i
tomer finish all work – ventilation unit
cannot be moved once the piping has
been connected.
Use the wall bracket and two rubber
i
pads supplied. The rubber buffers are
already fitted on
Provide sufficient working space for op-
i
erational and maintenance work. Keep
at least 70 cm in front of the unit free.
170
170
.
NOTICE
Function will be impaired by condensate:
The ventilation unit must be installed hori-
zontally so that the condensate can drain off
unhindered.
1. Install rail [S2] on wall with appropriate
mounting material. Rail [S1] is pre-
installed. Suitable mounting material
is to be supplied by the customer.
Make sure it is horizontal.
310/410 320/470
2.
pads [G] on the bottom corners of the
unit's rear as spacers.
3. Fit ventilation unit in rail [S2]. Retaining
plate and rail must cover one another
completely, the unit must make contact
with both rubber pads on the wall.
10.4 Mounting Flat unit on the ceiling or
wall
Flat
WARNING Chapter 10.1
!
Before installing, have customer finish
i
all work – ventilation unit cannot be
moved once the piping has been
connected.
Ensure sufficient space for the add-on
i
components.
Provide sufficient working space for
i
operational and maintenance work.
Keep at least 70 cm in front of the unit
free.
Installation | UK
: Stick the two rubber
47