Operation at rated power
9300
Type
Operation without mains choke/mains filter
EVF9321−xV
EVF9322−xV
EVF9323−xV
EVF9325−xV
Operation with mains choke/mains filter
EVF9321−xV
EVF9322−xV
EVF9323−xV
EVF9324−xV
EVF9325−xV
EVF9326−xV
1)
Universal current−sensitive earth−leakage circuit breaker
2)
For short−time mains interruptions, use circuit breakers with tripping characteristic "C"
Operation with increased rated power
9300
Type
Operation with mains choke/mains filter
EVF9321−xV
EVF9322−xV
EVF9323−xV
EVF9324−xV
EVF9325−xV
1)
Universal current−sensitive earth−leakage circuit breaker
2)
For short−time mains interruptions, use circuit breakers with tripping characteristic "C"
EDKVF9333V DE/EN/FR 7.2
Standard devices in the power range 0.37 ... 11 kW
Mains connection: Fuses and cable cross−sections
Rated fuse current
Fuse
Circuit−breaker
[A]
[A]
2)
6
C6, B6
2)
6
C6, B6
10
B10
25
B20
2)
6
C6, B6
2)
6
C6, B6
10
B10
10
B10
20
B16
32
B25
Rated fuse current
Fuse
Circuit−breaker
[A]
[A]
2)
6
C6, B6
2)
6
C6, B6
10
B10
10
B10
20
B16
l
Electrical installation
Cable cross−section
Laying system L1, L2, L3, PE
B2
C
2
[mm
]
[mm
1
1
1
1
1.5
1
4
2.5
1
1
1
1
1.5
1
1.5
1
2.5
2.5
˘
4
Cable cross−section
Laying system L1, L2, L3, PE
B2
C
2
[mm
]
[mm
1
1
1
1
1.5
1
1.5
1
2.5
2.5
5
1)
FI
2
]
[mA]
300
300
1)
FI
2
]
[mA]
300
171