Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze 8200 motec Montageanleitung Seite 118

Vorschau ausblenden Andere Handbücher für 8200 motec:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

7
Commissioning
The most important codes for commissioning
Code
No.
Name
C0007
Fixed
v
configuration
of digital
uSEr
inputs
C0007
v
uSEr
(cont.)
116
Possible settings
Lenze
Selection
0
E4
0
CW/CC
W
1
CW/CC
W
2
CW/CC
W
CW/CC
3
W
4
CW/CC
W
5
CW/CC
W
j6
CW/CC
W
7
CW/CC
W
CW/CC
8
W
9
CW/CC
W
10
CW/CC
W
E4
11
CW/CC
W
12
CW/CC
W
13
CW/CC
W
CCW/QS
14
P
15
CCW/QS
P
16
CCW/QS
P
17
CCW/QS
P
18
CCW/QS
P
19
CCW/QS
P
EDK82MV222 DE/EN/FR 8.0
E3
E2
E1
DCB
JOG2/3
JOG1/3
PAR
JOG2/3
JOG1/3
QSP
JOG2/3
JOG1/3
PAR
DCB
JOG1/3
QSP
PAR
JOG1/3
DCB
TRIP set
JOG1/3
PAR
TRIP set
JOG1/3
PAR
DCB
TRIP set
QSP
PAR
TRIP set
QSP
TRIP set
JOG1/3
TRIP set
UP
DOWN
E3
E2
E1
DCB
UP
DOWN
PAR
UP
DOWN
QSP
UP
DOWN
CW/QSP
DCB
JOG1/3
CW/QSP
PAR
JOG1/3
CW/QSP
JOG2/3
JOG1/3
CW/QSP
PAR
DCB
CW/QSP
PAR
TRIP set
CW/QSP
DCB
TRIP set
IMPORTANT
Change under C0007 will be
copied to the corresponding
subcode of C0410. Free
configuration under C0410
sets C0007 = 255!
CW/CCW = CW
l
rotation/CCW rotation
DCB = DC−injection brake
l
QSP = Quick stop
l
PAR = Parameter set
l
ó
changeover (PAR1
PAR2)
– PAR1 = LOW, PAR2 =
HIGH
– The terminal must be
assigned to the function
"PAR" in PAR1 and PAR2.
– Configurations with "PAR"
are only allowed if C0988
= 0
TRIP set = external fault
l
Selection of
l
fixed setpoints
active
JOG1/3 JOG2/3
C0046
LOW
LOW
JOG1
HIGH
LOW
JOG2
LOW
HIGH
JOG3
HIGH
HIGH
L

Werbung

Inhaltsverzeichnis
loading