Herunterladen Inhalt Inhalt Diese Seite drucken

Parameter Description - WIKA TSD-30 Betriebsanleitung

Temperaturschalter
Vorschau ausblenden Andere Handbücher für TSD-30:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6. Commissioning, operation
6.4 Parameters

Parameter Description

GB
SP1 / SP2
Hysteresis function: Switch point switching output (1 or 2)
FH1 / FH2
Window function: Window high switching output (1 or 2)
RP1 / RP2
Hysteresis function: Reset point switching output (1 or 2)
FL1 / FL2
Window function: Window low switch output (1 or 2)
EF
Extended programming functions
RES
Return the set parameter to the factory settings
DS1 / DS2
Switch delay time, which must occur without interruption before any electrical signal change occurs
(SP1 or SP2)
DR1 / DR2
Switch delay time, which must occur without interruption before any electrical signal change occurs
(RP1 or RP2)
OU1
Switching function switching output (1 or 2)
OU2
HNO = hysteresis function, normally open
HNC = hysteresis function, normally closed
FNO = window function, normally open
FNC = window function, normally closed
UNIT
Changing units
(If the measuring range is outside the indication range, a unit switching is not possible and the UNIT
parameter is not indicated)
0SET
Offset adjustment (3 % of span)
DISM
Display value in display mode
ACT = Actual temperature value; LOW, HIGH = Minimum, Maximum temperature value
OFF = display off;
SP1 / FH1 = function switch point 1, RP1 / FL1 = function reset point 1,
SP2 / FH2 = function switch point 2, RP2 / FL2 = function reset point 2
DISR
Rotate display indicator by 180°
RHL
Clear the Min- and Max-value memories
PAS
Password input, 0000 = no password
Password input digit by digit
TAG
Input of a 16-figure alphanumeric measuring point number
18
WIKA operating instructions temperature switch model TSD-30

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis