Wiring

5
Wiring
WARNING
L
Danger! Electric voltage!
The entire connection of the device must take place while the device is de-energized.
The ground connection must be made before all other connections. Danger may arise if the
protective ground is disconnected.
Before commissioning the device, make sure that the supply voltage matches the voltage
specifications on the nameplate.
Provide suitable switch or circuit breaker in building installation. This switch must be
provided close to the device (within easy reach) and marked as a circuit breaker.
Overcurrent protection (rated current ≤ 10 A) is required for the power cable.
• Observe the terminal designation on the side of the device.
• The mixed connection of safety extra-low voltage and dangerous contact voltage to the
relay is permitted.
5.1

Electrical connection

A loop power supply (LPS) is provided for every input. The loop power supply is primarily
designed to supply power to 2-wire sensors and is galvanically isolated from the system and
the outputs.
34
RMA42
Endress+Hauser