2

Technical data

2.1

Standards and operating conditions

Conformity
CE
Approvals
UL 508C
Vibration resistance
Acceleration resistant up to 2g (Germanischer Lloyd, general conditions)
Climatic conditions
Storage
IEC/EN 60721−3−1
Transport
IEC/EN 60721−3−2
Operation
IEC/EN 60721−3−3
Permissible site altitude
0 ... 4000 m amsl
Derate rated output by 5 %/1000 m above 1000 m amsl
Mounting positions
Any mounting position is possible
Mounting clearances motec
Above
To the sides
Mounting clearances fan
For replacing fan
module E82ZMV
Operation with fan module
The fan module E82ZMV must always be used in the case of
·
E82ZMV
motec wall mounting
·
operation without current derating with self−ventilated Lenze motors or Lenze geared motors ^ 68
·
operation with non−Lenze motors
L
efesotomasyon.com - Lenze
Standards and operating conditions
Low−Voltage Directive (73/23/EEC)
Underwriter Laboratories (file no. E132659)
Power Conversion Equipment
1K3 (−25 °C...+60 °C)
2K3 (−25 °C...+70 °C)
3K3 (−20 °C...+60 °C)
Derate the rated output current by 2.5 %/°C above +40 °C
100 mm
100 mm
250 mm
EDK82MV752 DE/EN/FR 6.0
Technical data
67