Show/Hide Bookmarks
Terminal strips on the bottom of the instrument
Analog
Analog
inputs
i
t
Analog
outputs
outputs
system bus
system bus
(CAN)
(CAN)
Tip!
l
l
X5
GND
LOW
HI
Abb. 1-19
120
Terminal Use
X4/AI1
Freely assignable input 1
X4/AI2
Freely assignable input 2
X4/AI3
Freely assignable input 3
X4/AOV
Voltage output
X4/AOI
Current output
X4/A⊥
Ground for analog inputs
and outputs
X5/GND
CAN-GND
X5/LOW
CAN-LOW
X5/HI
CAN-HIGH
A detailed description of how to invert the digital input and output levels can be found
in the section "DIGITAL_IO" of the Manual for the Drive PLC Developer Studio (DDS).
Use the function block L_AIN or L_AOUT to adjust the analog input and output signals.
A description of this can also be found in the section "Standard Library 9300 Servo
PLC" of the DDS Manual.
Control connections
X4
CAN-CG
CAN-LO
CAN-HI
PES
level
-10 V ... + 10 V
10 V ... + 10 V
-10 V ... + 10 V / max.
2 mA
-20 mA ... + 20 mA
-
Reference potential
System bus LOW
(data cable)
System bus HIGH
(data cable)
MA DrivePLC DE/EN/FR 1.0
AI1
AI2 AI3
A
AOV AOI
Data
Resolution: 10 bit + sign
Resolution: 10 bit + sign
Resolution: 10 bit + sign
Resolution: 10 bit + sign
-
-
-
-
3
plc003
9