RIA452
!
Function (menu item)
Signal type
Endress+Hauser
6
Commissioning
6. 1
Function check
Make sure that all post-connection checks have been carried out before you commission your
device:
• Checklist Section 4.3 'Post-connection check'
Note!
Remove the protective strip from the display as this restricts display legibility otherwise.
6. 2
Switching on the measuring device
Once the operating voltage is applied, the green LED indicates that the instrument is operational.
• When the unit is delivered, the device parameters are used as per the factory settings.
• When commissioning a device already configured or preset, measuring is immediately started as
per the settings. The limit values only switch once the first measured value has been determined.
• The limit values are only activated as per their configuration once a valid measured value is
present.
6. 3
Device configuration
This section describes all the configurable instrument parameters with the associated value ranges
and factory settings (default values, marked in bold).
6.3.1
Analog input - INPUT/M1
All the parameters that can be selected for the input can be found under the analog input menu item
which is marked as INPUT in the device.
Parameter setting
4 - 20 mA
0 - 20 mA
0 - 5 mA (*)
0 - 100 mV (*)
0 - 200 mV (*)
0 - 1 V (*)
0 - 10 V (*)
± 150 mV (*)
± 1 V (*)
± 10 V (*)
± 30 V (*)
Type B (IEC584) (*)
Type J (IEC584) (*)
Type K (IEC584) (*)
Type L (DIN43710) (*)
Type L (GOST) (*)
Type N (IEC584) (*)
Type R (IEC584) (*)
Type S (IEC584) (*)
Type T (IEC584) (*)
Type U (DIN43710) (*)
Type D (ASTME998) (*)
Type C (ASTME998) (*)
Description
Selects the signal type of the connected sensor. Parameters marked with an aster-
isk (*) can only be selected with the universal input option.
Commissioning
77