Alarm mode
Al: abs
Absolute alarm. The programmed alarm has a fixed reference to
the scaling range.
Al: re l
Relative alarm. The programmed alarm has a fixed reference to
the setpoint.
Alarm limit
PV+:
High alarm limit
Adjustment range:
PV-:
Low alarm limit
Adjustment range:
Hy:
Alarm hysteresis
Adjustment range:
Filter 1
An interference signal superimposed on the measured signal can be attenuated with
the filter. The filter consists of a low pass filter of the 1st order.
Fg1:
Limiting frequency (-3 dB) of input filter 1
Adjustment range:
0.1 Hz:
20 Hz:
Sub-menus of the main menu option Input 2
Signal type
Frequency
Input for a frequency-analog signal
0...10 V
Input for 0..10 V standard signal
0...20 mA
Input for 0..20 mA standard signal
4...20 mA
Input for 4..20 mA standard signal
Root extraction
√ : off
Root extraction function off
√ : on
Root extraction function on
DIGITAL INDUSTRIAL CONTROLLER
Pv- ≤ PV+ ≤ PVh
PVl ≤ PV- ≤ PV+
0.1 ≤ Hy ≤ 20.0 (in %, related to the
scaling rangePVl, PVh, or, if these can not
be set, to the size of the measuring range.
0.1 ≤ Fg1 ≤ 20.0 (in Hz)
strong damping (time constant = 1.6 sec)
weak damping (time constant = 0.01 sec)
1110 - 57