Herunterladen Diese Seite drucken

Linde MANIFOLD S200 Gebrauchsanleitung Seite 6

Werbung

ENGLISH
INSTRUCTION FOR USE: MANIFOLD
EN
1. GENERAL
1.1. INFORMATION ABOUT THIS INSTRUCTIONS MANUAL
This instruction is only intended for use with manifold product type:
S300/S200/S60
S203
S200
S60
Manifolds of this type are suitable to take gas out of gas cylinder or bundle and reduce the pressure. These
manifolds were installed as permanently wall assembly and are connected to gas cylinder or bundle with
coil or hose.
These instructions enable you to operate the system safely and effi ciently. These instructions form an inte-
gral part of the system and must always be kept with the system and within easy reach of staff at all times.
Prior to commencing any work, the staff must read these instructions carefully and understand the contents.
Observance of all the safety information and instructions for operation that are contained in these instruc-
tions is essential to ensure work safety.
Local accident prevention regulations and general safety regulations governing the use of the system must
also be observed.
Illustrations in these instructions serve to ensure a basic understanding of the system and may diff er from
the actual version.
1.2. INFORMATION ABOUT THIS MANIFOLD
Manifolds of this type are only suitable for gases defi ned as standard gas. The maximum working pressure
for these manifolds is 300 bar.
Single stage manifolds consists of valves and a pressure regulator with metal diaphragm, created and
approved as ISO7291/ISO10297 including oxygen shock test.
Product line
High Pressure Regulator
with
FKM
Relief Valve Seat
(Purity 6.0 | Brass chrome plated)
Suitable Gases
(including their mixtures)
High Purity
Inert
Flammable
Oxidizing
Use for O2
Not Suitable Gases
(including their mixtures)
Corrosive
Toxic
CO2, N2O
4/380
(Purity 6.0 | stainless steel)
Suitable Gases
(including their mixtures)
High Purity
Inert
Flammable
O2 up to 200 bar
Corrosive (in doubt ask)
Toxic (in doubt ask)
Not Suitable Gases
(including their mixtures)
O2 (above 200 bar)
CO2, N2O
NH3, SO2, H2S