Herunterladen Diese Seite drucken

Mitsubishi Electric Mr.SLIM SEZ-M25DA2 Installationshandbuch Seite 20

Vorschau ausblenden Andere Handbücher für Mr.SLIM SEZ-M25DA2:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 25
8. Electrical work
Function table 1
Select unit number 00
Mode
Power failure automatic recovery
(AUTO RESTART FUNCTION)
Indoor temperature detecting
LOSSNAY connectivity
Smart Defrost *3
Function table 2
Select unit numbers 01 to 04 or all units (AL [ wired remote controller] /07 [ wireless remote controller] )
Mode
Filter sign
External static pressure
Fan speed during the cooling thermostat is OFF
*1 When the power supply returns, the air conditioner will start 3 minutes later.
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.
*3 It is available when the indoor unit is connected to any of the particular outdoor units.
Note: When the function of an indoor unit were changed by function selection after the end of installation, always indicate the contents by entering a
appropriate check filed of the tables.
8.7. Rotation setting
You can set these functions by wired remote controller. (Maintenance monitor)
[Fig. 8-7-1] (P.9)
① Select "Service" from the Main menu, and press the [ SELECT] button.
② Select "Settings" with the [ F1] or [ F2] button, and press the [ SELECT] button.
③ Select "Rotation setting" with the [ F1] or [ F2] button, and press the [ SELECT]
button.
[Fig. 8-7-2] (P.9)
④ Set the rotation function.
• Select "Rotation" with the [ F1] button.
• Select the switching period or "Backup only" with the [ F2] or [ F3] button.
⿎ "Rotation" setup options
None, 1 day, 3 days, 5 days, 7 days, 14 days, 28 days, Backup only
Notes:
• When 1 to 28 days are selected from the setup options, the backup function
is also enabled.
hen "Backup only" is selected, the rotation function
systems with refrigerant addresses of 00 or 01 (00 system/ 01 system) will
be operated as a main system while the 02 system is the standby mode as
backup.
20
Settings
Not available
Available
Indoor unit operating average
Set by indoor unit's remote controller
Remote controller's internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
Available
Not available
Settings
100 Hr
2500 Hr
No filter sign indicator
25 Pa
35 Pa
50 Pa
The same as setting of mode no.08
5 Pa (set mode no. 08 to 1)
Setting fan speed
Stop
Extra low
[Fig. 8-7-3] (P.9)
⑤ Set the support function.
⿎ "TempDifTrigger" setup options
Notes:
• The support function is available only in the COOL mode. (Not available in
• The support function is enabled when any option other than "None" is
⑥ Press the [ SELECT] button to update the setting.
ill be disabled. The
Mode no.
01
*1
02
03
20
Mode no.
07
08
10
27
• Select "TempDifTrigger" with the [ F1] button.
• Select the difference between the suction temperature and the set
temperature with the [ F2] or [ F3] button.
None, +4°C, +6°C, +8°C
the HEAT, DRY and AUTO mode.)
selected from the "Rotation" setup options.
Reset method
• Press the [ F4] button in step ④ or ⑤ to reset the operation time of the rotation
function. Once it is reset, operation will start from the systems with refrigerant
addresses of 00 or 01.
Note: When the system with refrigerant address of 02 is in the backup operation,
the 00 or 01 systems will be operated again.
Setting no. Initial setting
Check
1
*2
2
*2
1
2
3
1
2
3
1
2
Setting no.
Initial setting
Check
1
2
3
1
2
3
1
2
1
2
3
or other mark in the

Werbung

loading