4.2.1 115/230 V and 24/48 V Changeover

By means of a jumper inside the unit, the supply voltage can be changed from 230 V
to 115 V, or from 12 V to 24 V respectively. This adaptation must take place before
installing the unit.
Procedure:
è Insert all connection and supply lines
è Remove the connecting screw for the Technical Earth
è Remove the optionally-installed interface card (if present)
è Undo the four screws on the rear plate, and remove the rear plate
è Pull the unit one third of the way out of the housing
è The jumper is easily accessible on the power supply printed-circuit board,
positioned immediately in front of one of the relays and identified by the numbers
1-4 on the board.
è At delivery, the connector is positioned between contacts 2 and 4
è To change the unit to 115V or 12 V respectively, contacts 1 and 3 must be
bridged with the connector. Proceed identically when changing from 24V to 12V.
è Finally, push the unit back into the housing, and screw on the rear plate.
NOTE
4.2.2 24V DC/AC Converter for operation at 24 V DC
The 12/24V AC controller model can also be operated at 24 VDC using an optional
DC/AC converter. Up to 3 controllers can be supplied from a single converter. (Order
number: 19139J)
Supply voltage
Output voltage
Efficiency
Switch-on delay
Dimensions (WxHxD)
104
DIGITAL INDUSTRIAL CONTROLLER
If the unit is to be set to the lower voltage, please ensure that the
voltage does not exceed the quoted tolerances, and make a note
on the wiring diagram.
16V-26V AC (50 Hz)
max. 5 secs
23 x 75 x 110 mm
16V - 26V DC
> 95%
3