Floor Sensor Calibration

Page 49
© 2016 OJ Electronics A/S
All manuals and user guides at all-guides.com
This option allows you to calibrate the floor sensor .
You should calibrate the sensor if the temperature reading differs from the actual
floor temperature .
Note that changes in the floor sensor characteristics may damage certain floors .
You can calibrate the sensor with +/- 10°C in steps of 0.5°C in the following way:
1 . Tap the "Menu" button on the home screen .
2 . Then tap the "engineer settings" button .
3 . Scroll down and tap the "Floor sensor Calibration" button .
4 . Confirm that you want to calibrate the sensor with "√" or cancel with "X" .
5 . If "√" is chosen, you must then offset the thermostat to reflect the floor
temperature actually measured .
6 . Use the "up arrow" or "Down arrow" button to set the measured floor
temperature .
7 . Confirm the value with "√" . A confirmation screen will be displayed briefly .
8 . The thermostat will automatically return to "engineer settings" .