Primary Device Functions (continued)
Manual Teach-in
In addition to the IO-Link-controlled teach processes, there
is the possibility of a manual teach-in. This is, in principle, a
Singe-Value Teach of setpoint 1 in the Single-Point
switching mode. With this process, only SSC 1 can be
taught. The teach process is started with the rising edge
on Pin 2. The now-active teach process is indicated by
illumination of the red LED.
If the LED switches off, the teach process has been ended
successfully. The sensor or SSC1 is now in Single-Point
Mode, the new setpoint is used as switching point in
combination with the standard hysteresis. The previous
configuration is discarded.
If the LED flashes for 3 seconds, the teach process was
not ended successfully. In this case, the previous
configuration continues to be used. The following error
causes are possible:
The current measurement value is outside of the
validity range.
The sensor cannot be parameterized locally. The
reasons for this are currently active ISDU
communication, an active block parameterization or set
access locks.
It is recommended that the manual teach process
is only used with inactive IO-Link communication
(in SIO modus).