10.4.4 Fault Ride-Through (FRT)

Description
This function is only available for MVD grids.
Menu:
530 FRT settings
Mode:
Main menu > User settings > FRT set-
tings
Example display:
03
5 3 0 F R T s e t t i n g s
- - - - - - - - -
M o d e :
k f a c t o r
Configurable parameters
Display text
Designation
Mode
Mode
k factor
k factor
DeadBand Vl
Deadband, lower
voltage limit
DeadBand Vh
DeadBand, upper
voltage limit
FRT delay t
FRT delay time
Max. I sym.
Maximum symmet-
ric current
Max I asym.
Maximum asym-
metric current
Operation and installation manual for SOLIVIA 11 EU G4 TR
- - - - - - - - - - %
O N
2
Description
Switches the function on
and off.
On | Off
0 ... 10
Lower voltage limit of the
deadband
184 ... 230 V
Upper voltage limit of the
deadband
231 ... 266 V
When the voltage once
more enters the deadband
then the maximum sym-
metric/asymmetric current
continues to be fed for the
specified delay time.
0.01 ... 5 s
Maximum reactive current
in the case of a symmetric
failure (= 3 phases)
0 ... 100 %
Maximum reactive current
in the case of an asymmet-
ric failure (= 2 phases)
0 ... 100 %
10.5

Options settings

Configurable settings

Shadowing

Isolation and grounding monitoring
Relay control
External stop
10.5.1 Shadowing
Description
The "Shadowing" option is an extended MPP tracker. When
the option is switched on the MPP tracker performs an addi-
tional search at regular intervals.
The MPP tracker then searches for the maximum power
over a wider voltage range.
This option should be switched on if shadows regularly pass
slowly over the PV modules in the course of a day. These
types of moving shadows can be caused by (e.g.) chimneys
or trees. This option has a relatively small effect in the case
of fast-moving shadows, e.g. from passing clouds.
The option is set depending on the size of the shadowing.
Menu:
210 Shadowing
Menu access:
Main menu > Options > Shadowing
Example display:
03
2 1 0 S h a d o w i n g
- - - - - - - - -
M o d e :
- - - - - - - - -
Configurable parameters
Display text
Designation
Mode
Mode
10. Settings
- - - - - - - - - -
D e a c t i v a t e d
- - - - - - - - - -
Description
Deactivated
Extended MPP tracking is
deactivated
High
High shadowing,
time cycle: 0.5 hour
Medium
Medium shadowing,
time cycle: 2 hour
Low
Low shadowing,
time cycle: 4.5 hour
43