10. Settings

10.5.2 Isolation and grounding monitoring

Description
The DC side of the solar power inverter has an isolation and
grounding monitor.
The isolation monitoring offers two modes:
ISO Failure
ISO Warning
If the positive or negative pole of the PV modules must be
grounded to satisfy the requirements of the module manu-
facturer then this grounding can be monitored. The ground-
ing monitoring has four modes:
– GND Failure
– GND Warning
+ GND Failure
+ GND Warning
Before delivery, the solar power inverter is set at the factory
to the ISO Warning (Isolation warning) mode.
Description of the monitoring modes:
Monitoring mode
Description
ISO/GND off
Monitoring is deactivated.
xxx failure
If an isolation failure occurs the solar
power inverter is disconnected from
the grid.
xxx warning
If an isolation failure occurs the solar
power inverter logs and displays the
failure but is not disconnected from
the grid.
Menu:
230 Grounding
Menu access:
Main menu > Options > Grounding
Example display:
03
2 3 0 G r o u n d i n g
- - - - - - - - -
P V :
- - - - - - - - -
Configurable parameters
Display text
Designation
PV
PV monitoring
44
- - - - - - - - - -
I S O W a r n i n g
- - - - - - - - - -
Description
ISO Failure
ISO Warning
– GND Failure
– GND Warning
+ GND Failure
+ GND Warning
ISO/GND off

10.5.3 Relay control

Description
Two relays can be controlled independently of each other
via the I/O interface.
Menu:
240 Relay control
Menu access:
Main menu > Options > Dry contact
Example display:
03
2 4 0 R e l a y c o n t r o l
- - - - - - - - -
C t l . R e l a y 1
C t l . R e l a y 2
03
2 4 1 C t l . R e l a y 1
- - - - - - - - -
M o d e :
S u p p l y
Configurable parameters
Display text
Designation
-
Signal type

10.5.4 External stop

Description
An external signal for stopping the feeding of energy into
the grid can be sent to the solar power inverter via the I/O
interface. After being enabled, the signal level to stop feed-
ing can be configured as a HIGH or LOW signal.
Menu:
250 External stop
Menu access:
Main menu > Options > External stop
Example display:
03
2 5 0 E x t e r n a l s t o p
M o d e :
A c t i v e :
Configurable parameters
Display text
Designation
Mode
Activate/Deactivate
function
Active
Active signal level
Operation and installation manual for SOLIVIA 11 EU G4 TR
- - - - - - - - - -
- - - - - - - - - -
A c t i v a t e d
Description
Supply
Temp. too high
User setting
External stop
Failure
Warning
Feed-in ongoing
O n
H I G H
Description
On | Off
HIGH | LOW