Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection; Shielding And Cable Routing - Balluff BIR 01 K12LL3-000S04 Serie Betriebsanleitung

Schnelles induktives positionsmesssystem
Vorschau ausblenden Andere Handbücher für BIR 01 K12LL3-000S04 Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
BIR 01- _ _ _ _ -K12LL3-000S04
Inductive Rapid Positioning System
5
Installation and connection (continued)
5.3

Electrical Connection

The electrical connection is made via a plug connection
(for pin assignment see Tab. 5-2).
3
4
2
1
Fig. 5-6:
Pin assignment of S04 (view from above on BIR)
Pin
Signal
1
18...30 V
2
Not assigned
3
4
C/Q (communication line)
Reference potential for supply voltage and EMC-GND
1)
Tab. 5-2:
Pin assignment S04
5.4

Shielding and cable routing

Defined ground!
The BIR and the control cabinet must be on the
same ground potential.
Shielding
Observe the following instructions to ensure
electromagnetic compatibility (EMC):
Connect BIR and controller using a shielded cable.
Shielding: Braided copper shield with minimum 85%
coverage.
Shield is internally connected to connector housing.
www.balluff.com
GND
1)
Cable routing
Do not route the cable between the BIR, controller, and
power supply near high voltage cables (inductive stray
noise is possible). The cable must be routed tension-free.
Only approved cables with a minimum size of
AWG 24 may be used. All connected cables
must have a temperature resistance of at least
85 °C. Use copper conductor, only.
Cable length
For IO-Link operation, the maximum cable length is 20 m.
english
13

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis