Drive type
Frame size
ACQ580-34-
365A-4
R11
442A-4
R11
505A-4
R11
585A-4
R11
650A-4
R11
U
= 480 V, IEC
n
246A-4
R11
293A-4
R11
365A-4
R11
442A-4
R11
505A-4
R11
585A-4
R11
650A-4
R11
U
= 480 V, UL (NEC)
n
240A-4
R11
302A-4
R11
361A-4
R11
414A-4
R11
477A-4
R11
These losses are not calculated according to IEC 61800-9-2.
Typical power cable sizes
Drive type
ACQ580-34-
Cu cable type
U
= 400 V, 480 V (IEC)
n
246A-4
2 × (3 × 70 + 35)
293A-4
2 × (3 × 95 + 50)
365A-4
2 × (3 × 120 + 70)
442A-4
2 × (3 × 150 + 70)
505A-4
3 × (3 × 95 + 50)
585A-4
3 × (3 × 120 + 70)
650A-4
3 × (3 × 150 + 70)
U
= 480 V, UL (NEC)
n
240A-4
2 × (3 × 70 + 35)
302A-4
2 × (3 × 95 + 50)
361A-4
2 × (3 × 120 + 70)
414A-4
2 × (3 × 150 + 70)
477A-4
3 × (3 × 95 + 50)
Air flow
3
m
/h
2100
2100
2100
2100
2100
2100
2100
2100
2100
2100
2100
2100
2100
2100
2100
2100
2100
1)
IEC
Al cable type
2
mm
2 × (3 × 95)
2 × (3 × 120)
2 × (3 × 185)
2 × (3 × 240)
3 × (3 × 150)
3 × (3 × 185)
3 × (3 × 240)
2 × (3 × 95)
2 × (3 × 150)
2 × (3 × 185)
2 × (3 × 240)
3 × (3 × 150)
Technical data and references 123
Heat dissipation
3
ft
/min
1236
8000
1236
10000
1236
10000
1236
12600
1236
14200
1236
5220
1236
5220
1236
7830
1236
9135
1236
9135
1236
9135
1236
10440
1236
5280
1236
6525
1236
7830
1236
9135
1236
10440
2
mm
2 × 500 MCM or 3 × 250 MCM
2 × 600 MCM or 3 × 300 MCM
2 × 700 MCM or 3 × 350 MCM
2 × 500 MCM or 3 × 250 MCM
Noise
W
dB(A)
72
72
72
72
72
72
72
72
72
72
72
72
72
72
72
72
72
2)
UL (NEC)
Cu cable type
AWG/kcmil
2 × 2/0
2 × 3/0
2 × 250 MCM
2 × 400 MCM
2 × 2/0
2 × 4/0
2 × 250 MCM
2 × 350 MCM
EN
DE
ES
FR
IT
TR