Fig. 16: Pump cycling
Behaviour of the inputs and outputs
Fault and run signals
Installation and operating instructions Wilo-CronoLine-IL-E, CronoTwin-DL-E, CronoBloc-BL-E
Pump 2
• Pump 1 turns (black line)
• Pump 2 is switched on at minimum speed and soon afterwards
• Pump 1 is switched off
• Pump 2 continues to run until the next pump cycling
t
• At the master: acts on the whole unit
• Set at the master (menu <5.1.7.0>): depending on the setting in menu
• Set at the slave: acts only on the slave
• A collective fault signal (SSM) can be connected to the master for a
• In this case, the contact may only be made to the master.
• The display is for the whole unit.
• This signal can be programmed on the master (or using the IR-Moni-
• The contact must be made to each pump for individual fault signals.
• A collective run signal (SBM) can be connected to the master for a
• In this case, the contact may only be made to the master.
• The display is for the whole unit.
• This signal can be programmed on the master (or using the IR-Moni-
• The functions - "Readiness", "Operation", "Mains on" - from EBM/
• The contact must be made to each pump for individual run signals.
• Externally (menu <5.1.3.2>) by a positive edge at the "AUX" contact
(See Fig. 27)
• Manually, (menu <5.1.3.1>)
Manual or external pump cycling is possible five seconds after the last
pump cycling, at the earliest.
Activation of external pump cycling simultaneously deactivates
internal time-controlled pump cycling.
Pump cycling can be described schematically as follows (see also Fig. 16):
reaches the setpoint (grey line)
NOTICE:
In manual control mode, a slight increase in flow can be expected.
Pump cycling is depending on the ramp time and generally lasts 2 s. In
auto control, there may be minor fluctuations in the delivery head.
However, pump 1 adjusts itself to the changed conditions. Pump
cycling is dependent on the ramp time and generally lasts 4 s.
Actual value input In1 setpoint input In2 (The input behaves as shown
in Fi g. 5 )
"External off":
<5.1.7.0>, acts only on the master or on the master and the slave
ESM/SSM:
central control centre.
tor/IR-Stick) as an individual fault signal (ESM) or a collective fault
signal (SSM) in menu <5.1.5.0>.
EBM/SBM:
central control centre.
tor/IR-Stick) as an individual run signal (EBM) or collective run signal
(SBM) (menu <5.1.6.0>).
SBM can be set at <5.7.6.0> on the master.
NOTICE:
"Readiness" means:
The pump could run, there is no fault.
"Operation" means:
Motor turning.
"Mains on" means:
Mains voltage is present.
NOTICE:
If EBM/SBM is set to "Operation", EBM/SBM is activated for a few sec-
onds when pump kick is executed.