Herunterladen Inhalt Inhalt Diese Seite drucken

In- / Outputs; Inputs; Outputs - Resol DeltaTherm HC mini Handbuch Für Den Fachhandwerker

Heizungsregler
Vorschau ausblenden Andere Handbücher für DeltaTherm HC mini:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

13

In- / Outputs

In the In- / Outputs menu, sensor offsets can be adjusted and relay outputs con-
figured.
Note:
The Gateways submenu has no function!
13.1

Inputs

In this submenu, the type of the sensor connected can be adjusted for each indi-
vidual input. The following types can be selected:
• Pt1000
• Switch (S4 only)
• RTA (S5 only)
• None
ATTENTION!
System damage!
Selecting the wrong sensor type will lead to unwanted controller
actions. In the worst case, system damage can occur!
Î Make sure that the right sensor type is selected!
If Pt1000 has been selected, the channel Offset appears, in which an individual
offset can be adjusted.
1.
In order to select a sensor for the offset adjustment, select the corresponding
menu item by pressing the right button (✓).
2.
In order to make an adjustment, adjust the desired value with the Lightwheel
and confirm with the right button (✓).
In- / Outputs / Inputs
Adjustment
Description
channel
S1 ... S5
Sensor input selection
Type
Sensor type selection
Offset
Sensor offset
Inverted switching option
Inverted
(only if Type = Switch)
13.2

Outputs

In this menu, the signal type and the minimum speed can be adjusted for each relay.
Î In order to make adjustments for a relay, select the corresponding menu item
by pressing the right button (✓).
For each relay, the signal type and the minimum pump speed can be adjusted. The
parameter Minimum speed will not be available for R4, if the signal type Standard
has been selected.
Adjustment range / selection
-
Switch (S4 only), RTA (S5 only), BAS (S5
only), Pt1000, none
-15.0 ... +15.0 K
Yes, No
®
Factory
setting
-
Pt1000
0,0 K
No
37