15 Commissioning software
• Settings: Basic system settings for the special-
ist installer, such as number/selection of device
types, function selection 230 V input etc.
• Instructions: Information/PDF instructions for
the specialist installer
• Complete commissioning/maintenance: To
save a commissioning or maintenance protocol.
This includes project data, information regard-
ing the planner, installer and customers as well
as notes. The unit date, all settings and a fault
logbook are automatically input.
• Input/read out data set: To read out or input
the device configurations. This can, for ex-
ample, be sent to the manufacture in case ser-
vicing is needed. Externally created configura-
tion data can be input.
Basic settings – Specialist installer
Parameters
Luminosity of LED in-
dicator
Luminosity of LED
standby
Automatic operation
LED standby
Selection of unit type
PP 45 / PPB 30 O
Quantity of units PP
45 / PPB 30 O
Set value
2, 3, 4, 5
0, 1, 2
0 ... 3 ... 6 minutes
PP 45, PPB 30 O
1 PP 45 / 1 PPB 30 O
unit pair
2 PP 45 / 2 PPB 30 O
unit pairs
3 PP 45 / 3 PPB 30 O
unit pairs
3 PP 45 units, operation
with odd number of
units
Parameters
Quantity of PPB 30 K
PPB 30 K
operating mode
PPB 30 K
sensor function
PPB 30 K
button function
PPB 30 K
start delay button
PPB 30 K
duration button function
No. of power units
RLS 45 K function
230 VAC input
Function Supply air
function Overrun time
Modbus
communication
Modbus baud rate
Modbus address
Restore factory settings Keep settings
If the RS-485 interface is configured as a
Modbus interface, no further components
(sensors, power units, room air controls etc.)
can be connected at this interface.
Set value
5 PP 45 units, operation
with odd number of
units
No PPB 30 K
1 PPB 30 K
2 PPB 30 K
3 PPB 30 K
Automatic operation
system operation
Exhaust air mode
intensive ventilation
Exhaust air mode
intermittent ventilation
0 ... 120 sec.
5 ... 10 ... 90 min.
No further LTs/RLS
1 LT/RLS
2 LTs/RLS
3 LTs/RLS
Slave no. 1
Slave no. 2
Slave no. 3
Sleep function
intermittent ventilation
safety function
supply air function
No overrun time
6 min. overrun time
15 min. overrun time
deactivated
activated
9600 baud
19200 baud
10 ... 50
restore factory settings
55