Endress+Hauser Proline Prosonic Flow P 500 Installationsanleitung Seite 27

Austausch sensor, sensorhalterung, installations set
Vorschau ausblenden Andere Handbücher für Proline Prosonic Flow P 500:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3.
With measuring wire 2: fit the cable lug over the mounting bolt of strapping band 1 that
is already securely mounted. Run measuring wire 2 counterclockwise around the
measuring pipe. Fit the fixer over the mounting bolt of strapping band 2 that can still be
moved.
4.
Take the still movable strapping band 2, incl. the mounting bolt, and move it until both
measuring wires are evenly tensioned and then tighten strapping band 2 so that it
cannot slip. Then check the sensor distance from the center of the strapping bands. If
the distance is too small, release strapping band 2 again and position it better. Both
strapping bands should be as perpendicular as possible to the measuring pipe axis and
parallel to one another.
 13
Positioning the strapping bands (steps 2 to 4)
5.
Loosen the screws of the fixers on the measuring wires and remove the measuring wires
from the mounting bolt.
6.
Fit the sensor holders over the individual mounting bolts and tighten securely with the
locking nut.
 14
Mounting the sensor holders
Endress+Hauser
13 mm
EA01368D
27