Function and features
The CR2011 output module enables decentralised triggering of actuators and
proportional valves. The coil current can be monitored and controlled via the inte-
grated current measurement.
• The module supports binary and analog outputs and is therefore classified in
the device profile "I/O module" to CiA DS 401.
• As regards the output function the module can be configured. The module
supports 5 operating modes:
- binary outputs with current detection, up to 2.5 A
- binary outputs without current detection, up to 4 A
- PWM outputs with current detection, up to 2.5 A
- PWM outputs without current detection, up to 4 A
- current-controlled PWM outputs, up to 2.5 A
The function current detection or current control can be selected by means of
the wire connection. With the configuration as binary outputs 8 outputs are
available. With the configuration as PWM outputs 2 outputs each are com-
bined as a pair (= 4 outputs available).
• The outputs are activated via CANopen.
• There are 1 server SDO and the 3 default PDOs to CiA DS 401. The PDO map-
ping cannot be changed (static PDO mapping). The default identifiers are
assigned according to the "predefined connection set".
• The COB IDs of the PDOs as well as the transmission type (synch/asynch) of the
individual PDOs can be configured. The transmission type is stored nonvolatile-
ly. Changed PDOs (PDO linking) are stored volatilely.
• The module expects a synch object.
The CAN identifier of the synch object can be configured. After a change the ID
is automatically stored non-volatilely.
• The module supports "node guarding".
The "guard time", "life time factor" and the CAN identifier of the guard
object can be configured and are stored non-volatilely.
• The module generates an emergency object. The COB ID of the EMCY object
can be configured.
• The module stores the last 4 errors. The error code of the corresponding emer-
gency object is stored.
• The module supports a reset function, i.e. assignment of the parameters to the
factory default values* upon request.
*) factory default values see „Parameter list", page 30