Object directory
Communication Profile Area; index 1000 to 1FFF
Index S-idx Designation
Life Time
100D
0
Factor
COB ID
100E
0
Guarding
Number of
100F
0
SDOs
Number of
0
save options
1010
"save all
1
parameters"
Number of
0
restore options
1011
"reset for all
1
parameters"
COB ID
1014
0
Emergency
0
Server SDOs
COB ID
1200
1
Rec SDO
2
Server SDOs
Receive
0
PDO 1
1
COB ID
1400
2
Trans Type
All manuals and user guides at all-guides.com
Type
Default
If no "node guarding" is received for "guard
time" x "life time", the output module switches
u8, rw
the outputs off. The CANopen state is not
0x00
changed. The result from "guard time" x "life
time" must be between 0 and 65535.
0x00000700
u32, rw
CAN identifier of the node guard object
+ Node ID
Not implemented, only the default SDO is sup-
ported.
u8, ro
0x01
Number of the "save" options
All parameters are automatically saved after a
u32, rw
0x02
change.
u8, ro
0x01
Number of the "restore" options
If the string "load" is entered here, the parame-
u32, rw
0x01
ters are assigned to the factory default values
and are valid after the next reset.
- Output module does not react to external
- Output module generates EMCY message
0x40000080+
u32, rw
Node ID
- 11-bit ID (bit 29 = 0)
- ID = 0x80 + node ID
CAN identifier can be changed by the user.
u8, ro
0x02
Number of the entries
0x600
- SDO is valid (bit 31 = 0)
u32, ro
+ID
- CAN ID of the receive SDO
0x580
- SDO is valid (bit 31 = 0)
u32, ro
+ Node ID
- CAN ID of the transmit SDO
Number of the entries receive PDO1
u8, ro
0x02
Binary outputs
0x200
- PDO is valid (bit 31 = 0)
u32, rw
+ Node ID
- CAN ID of the 1st receive PDO
0 x 00 = synch acyclic
0x01...0xF0 = synch cyclic, number of the synch
objects between two accesses
0xFC / 0xFD = not implemented
u8, rw
0x01
0xFE = asynch manuf. specific event, outputs
are updated immediately
0xFF = asynch device profile event, outputs are
updated immediately
OUTPUT MODULE
Description
EMCY message (bit 31 = 1)
(bit 30 = 1)
CR2011
35
PAGE