4 OPERATION

4.3 Setting up

The following basic settings are to be carried out on the initial setting up (commissioning) of the posi-
tioner in conjunction with the valve (specification of basic functions):
- Specification of the positional feedback of the continuous valve to the positional transducer (direct or
lever),
- Specification of the unit signal input chosen for entering the set position (0 ... 20 mA, 4 ... 20 mA or 0
... 10 V),
- Initiating the automatic adaptation of the actuator to the valve being used.
When the power is switched on, the positioner is in the process control level. It is necessary to switch
to the configuration level for specification of the basic functions. To do this, press the MANUAL/AUTO-
MATIC key and hold for 5 seconds. The first menu point X-SENS of the main menu is then displayed.
Fig. 24 Main menu for fi rst setting up
Function
AUTOMATIC
or
MANUAL
POSITIONER 1067
after 30 to 120 sec.
BLINKING
E-19-