Herunterladen Inhalt Inhalt Diese Seite drucken

Cleaning - elco THISION L 50 Betriebsanleitung

Vorschau ausblenden Andere Handbücher für THISION L 50:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

Maintenance

Cleaning

3
6
4
All manuals and user guides at all-guides.com
1
2
Cleaning the condens tray
gas temperature sensor (1);
Remove the condense tray (2);
Clean the tray;
Mount the condense tray;
temperature sensor.
Remove the syphon (3) from the
condensate connection;
Mount the syphon back in the ori-
ginal position.
Inspection of combustion
chamber
For inspection of the combustion
chamber the mixing system and bur-
ner must be disassembled.
Switch off the boiler and close the
gas supply;
Remove the electrical connection
from the fan and gas valve (4);
Remove the electrical connection
from the electrodes (5);
Undo the gas connection at the
inlet of the gas valve (6);
Disassemble the top plate incl.
mixing system (7);
Remove the burner from the
and clean it with a vacuum clea-
ner if necessary;
7
Assemble all components in op-
posite order;
Open the gas supply and check
all connections for gas leakage;
Switch on the boiler.