Vortice VORT NRG EC 3000 Bedienungs- Und Inbetriebnahmeanleitung Seite 34

Vorschau ausblenden Andere Handbücher für VORT NRG EC 3000:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

ENGLISH
Description
Display
Outdoor
Outdoor temperature
temp. probe
probe error
error
AS temp.
Supply air temperature
probe error
probe error
AR temp.
Return air temperature
probe error
probe error
Def. temp.
Defrost temperature
probe error
probe error
Supp. temp.
Defrost battery probe
regulator error
error
AS pressure
AN pressure probe error
probe error
AR pressure
AE pressure probe error
probe error
CO2 probe
CO2 probe error
error
Manual mode Ventilation in manual
mode
... Manual
Working in manual mode
NOTE: the first thing to check is that you do not have a "Manual" type fault
Type
Time
Cause
C
5 sec
The outdoor temperature probe SEG is not working or is wrongly
wired (see section V)
C
5 sec
The supply air temperature probe SSG is not working or is wrongly
wired (see section V)
C
5 sec
The return air temperature probe SRG is not working or is wrongly
wired (see section V)
C
5 sec
The defrost temperature probe SDG is not working or is wrongly
wired (see section V)
C
5 sec
The defrost battery probe SBD is not working or is wrongly wired
(see section V)
The resistor is not working or is wrongly wired
C
5 sec
The new air pressure transmitter is not working or wrongly wired
C
5 sec
The return air pressure transmitter is not working or wrongly wired
C
5 sec
The CO2 probe is not working or is wrongly wired
C
0 sec
This is not a fault but an alert message, the unit is not in AUTO, see
section VII.3.6
C
0 sec
You have touched a wrong parameter in the MANUAL AUTO tab
(everything should be in AUTO
34