10. Parameter configuration
10.1. Available parameters
4 different operating parameters can be changed in the control system.
Parameter
Description
14
Kiln output to determine the energy consumption in kW
45
Activate additional switch output
50
Time interval of the USB logging in seconds
60
Temperature unit in °C or °F
⇒ These parameters can be changed in the parameter level of the controller (see Section 10.).
10.2. Parameter details
Parameter no.
Parameter function
Kiln performance
14
display in kW
Additional switch
45
output 230 V
(ST 411 only)
Logging interval data
50
on USB in s
Temperature display in
60
°C or °F
⇒ To call up the kiln performance (parameter no. 14), see Section 6.7.!
10.3. Changing parameters
Step
Display screen
1
8.8.8.8.
2
tC.S
3
tC.S
4
Min. value
0
0
5
0
Icon
Description
Switching the control unit off
Switch on the control unit and
j
press the
key at the same time.
Hold down the
thermocouple type is shown in the
main display.
j
Release the
Max. value
Default setting
9999
0
3
0
300
60
1
0
Remark
⇒ The thermocouple type is only
j
key until the set
⇒ The thermocouple is preconfigured
key.
75 / 280
Description of the value
1 unit = 0.1 kW
E.g.:
For a kiln with an output of
10 kW (see kiln
nameplate), enter the value
"100".
0 = disabled
1 = event
2 = flap
3 = fan
1 unit = 1 s (second)
0 =°C
1 = °F
displayed and cannot be changed
here.
at the factory.