12 GEMÜ 9428 electrical connection
100-250 V AC (code 04)
Position of the connectors
Electrical connection
5
4
6
3
1
2
Plug assignment X1, UV
Pin
L1, supply voltage
1
N, supply voltage
2
L1, direction of travel CLOSED
3
N, direction of travel CLOSED
4
L1, direction of travel OPEN
5
N, direction of travel OPEN
6
PE, protective earth conductor
The potential must be assigned by the user.
Connection diagram
External wiring
Connection diagram X1, UV
GEMÜ R488 Victoria
Actuator version 3035, 3055
X1
X2
Description
OPEN
CLOSED
4
5
3
6
1
2
Actuator version 2006, 2015
UV
5
4
6
3
1
2
Plug assignment X2, S1/S2
Pin
1
Change-over contact limit switch CLOSED
2
Make contact limit switch CLOSED
3
Break contact limit switch CLOSED
4
Break contact limit switch OPEN
5
Make contact limit switch OPEN
6
Change-over contact limit switch OPEN
PE, protective earth conductor
L1
OPEN
N
PE
1
4
2
Connection diagram X2, S1/S2
112 / 136
S1/S2
Description
CLOSED
Additional
2
4
limit switches
5 4
6
3
2
1
www.gemu-group.com
1