12.1.2 On/Off actuator with 2 potential-free limit switches (code AE)
Always switch the limit switch for signal so that the motor switch is actuated first.
●
ð Limit switches for signal and motor are already preset.
12 V DC (code B1) / 24 V DC (code C1)
Position of the connectors
Electrical connection
5
4
6
3
1
2
Plug assignment X1, UV
Pin
Uv+, direction of travel CLOSED
1
Uv-, direction of travel CLOSED
2
Uv+, direction of travel OPEN
3
Uv-, direction of travel OPEN
4
n. c.
5
n. c.
6
PE, protective earth conductor
www.gemu-group.com
Risk of electric shock
▶ Death or injuries
The end positions (potential-free limit switches) are set mechanically by means of
●
adjusting screws. To do this, disconnect the plant from the power supply. This may
only be done by qualified electricians!
Actuator version 3035, 3055
X1
X2
Description
DANGER
NOTICE
Actuator version 1006, 1015
S1/S2 UV
5
4
6
3
1
2
Plug assignment X2, S1/S2
Pin
1
Change-over contact limit switch CLOSED
2
Make contact limit switch CLOSED
3
Break contact limit switch CLOSED
4
Break contact limit switch OPEN
5
Make contact limit switch OPEN
6
Change-over contact limit switch OPEN
PE, protective earth conductor
109 / 136
12 GEMÜ 9428 electrical connection
Description