7. Starting, operation
When mounting the instrument, ensure that the sealing faces of the instrument and
the measuring point are clean and undamaged.
Screw in or unscrew the instrument only via the flats using a suitable tool and the
prescribed torque. The appropriate torque depends on the dimension of the pressure
connection and on the sealing element used (form/material). Do not use the case as
working surface for screwing in or unscrewing the instrument.
When screwing the transmitter in, ensure that the threads are not jammed.
Do not torque the process controller with a force greater than 36,9 foot pounds
(50 Nm).
For tapped holes and welding sockets please see Technical Information IN 00.14 for
download at www.wika.de -Service
Protect the diaphragm against any contact with abrasive substances and
pressure peaks and do not touch it with tools. If you damage the diaphragm,
no intrinsic safety can be guaranteed (ATEX)!
Warning
Ensure that the pressure transmitter is mounted in a shielded section and
protect it against shocks.
Do not use the pressure transmitter out of the temperature range from
-40 ... +105 °C / -40 ... +221 °F. Out of this range there is no explosion
protection ensured.
Observe the permissible surface temperature applicable for this range according to the
defined temperature classes.
Install the transmitter using the appropriate mating process connection away from exces-
sive heat permissible temperature and vibration whenever possible.
Do not exceed the nominal pressure range for a prolonged period of time, because this
can lead to an inadmissible heating of the case.
Electrical connection
Always connect the case to earth to protect the pressure transmitter against
!
electromagnetic fields and electrostatic charges.
Warning
8
WIKA Operating instructions/Betriebsanleitung E-10, E-11