WWarning
• Leakage currents in the circuit following the residual current protection device may
influence measurements.
• The displayed fault voltage relates to the rated residual current of the RCD.
• Potential fields of other earthing installations may influence the measurement.
• Equi pment (motors, capacitors) connected downstream of the RCD may cause
considerable extension of the tri pping time.
Note: If the L and N terminals are reversed, the tester will auto-swap them internally and
continue testing. If the tester is configured for UK operation, testing will halt and you will
need to determine why the L and N are swapped.
This condition is indicated by symbol (
Type A and type B RCDs do not have the 1000 mA option available.
To measure RCD tri pping time:
1. Turn the rotary switch to the
2. Press F1 to select the RCD current rating (10, 30, 100, 300, 500, or 1000 mA).
3. Press F2 to select a test current multiplier (x ½, x 1, x 5, or Auto). Normally you will use x
1 for this test.
4. Press F3 to select the RCD test-current waveform:
– AC current to test type AC (standard AC RCD) and type A (pulse-DC sensitive RCD)
– Half-wave current to test type A (pulse-DC sensitive RCD)
– Delayed response to test S-type AC (time delayed AC RCD)
– Delayed response to S-type A (time delayed pulse-DC sensitive RCD)
– Smooth-DC current to test type B RCD
– Delayed response to S-type B (time delayed smooth-DC current RCD)
5. Press F4 to select the test current phase, 0° or 180°. RCDs should be tested with both
phase settings, as their response time can vary significantly depending on the phase
Note: For RCD type B (
settings, all three test leads are required.
6. Press and release
• The primary (upper) display shows the trip time.
• The secondary (lower) display shows the fault voltage related to the rated residual
current.
).
position.
) or S-type B (
. Wait for the test to complete.
), you must test with both phase
15