Advanced features of the digital controller
This chapter gives an overview and a brief functional description of
the screens provided by the different menus. In the following chapter,
you will find how you can set up and configure the unit using the
various menu functions.
The down arrow X on the display indicates that you can go to the next
screen of the current menu using the h key. The up arrow W on the
display indicates that you can go to the previous screen of the current
menu using the g key. If C is displayed, this indicates that you can
either return to the previous screen or can go to the next screen by
using the g and h keys.
Main menu
Scroll through the main menu using the g and h keys to move the >
mark in front of the menu of your choice. Push the q key to enter the
selected menu.
>READOUT MENU
SETPOINTS MENU
USERSETTINGS MENU
TIMERS MENU
HISTORY MENU
INFO MENU
I/O STATUS MENU
USERPASSWORD MENU
COOL/HEAT MENU
Readout menu
To consult actual operational infor-
BX MANUAL MODE
INL WATER E: 12.0°C
mation about the control mode, the
INL WATER C: 30.0 °C
inlet
THERMOSTAT STEP :2/6
evaporator/condenser
thermostat step.
To consult information about the
BC
EVAPORATOR
M1 : OUTLWATER: 07.0 °C
outlet water temperature of the
M2: OUTLWATER: 07.0 °C
modules 1,
M3: OUTLWATER:-03.0 °C
147~192).
To consult information about the
BC
COMPRESSOR STATUS
C11 : OFF-CAN STARTUP
compressor status (first screen).
C12: OFF-CAN STARTUP
C21: OFF-CAN STARTUP
To consult information about the
BC
COMPRESSOR STATUS
C22: OFF-CAN STARTUP
compressor status (second screen).
C31 : OFF- SAFETY ACT.
C32: OFF- LIMIT
To
BW
RUNNING HOURS
C11 : 00010h 12 ; 00010h
information about the total running
C21 : 00010h 22 ; 00010h
hours of the compressors.
C31 : 00010h 32 ; 00010h
Setpoints menu
Depending upon the settings in the user settings menu and on the
selected cooling/heating operation mode, the "setpoints" menu can
either be entered directly or by means of the user password.
To define the temperature setpoints.
B>INLSETP1 E : 12.0°C
INLSETP2 E : 12.0°C
INLSETP1 C : 30.0°C
INLSETP2 C : 30.0°C
Operation manual
9
water
temperature
of
the
and
the
2
and
3
(only
for
consult
actual
operational
User settings menu
The "user settings" menu, protected by the user password, allows a
full customization of the units.
To define the manual settings and to
BC
CONTROL SETTINGS
MODE :MANUAL CONTROL
select the control mode.
C11 : OFF 12 ; OFF
C21 : OFF 22 ; OFF
To define the thermostat settings.
BC
THERMOST.SETTINGS
STEPS : 6 STPL.: 1.5°C
STEPDIFFERENCE: 0.5°C
LOADUP: 180s-DWN: 30s
To define the lead-lag mode of the
C
LEAD-LAG SETTINGS
LEAD-LAG MODE : AUTO
modules.
LEAD-LAG HOURS: 1000h
To define capacity limitation.
BC
CAP. LIM. SETTINGS
MODE : REMOTE DIG INP.
(first screen)
L1M1 : OFF 2: OFF 3: OFF
L2M1 : OFF 2: OFF 3: OFF
To define capacity limitation.
BC
CAP. LIM. SETTINGS
L3M1 : OFF 2: OFF 3: OFF
(second screen)
L4M1 : OFF 2: OFF 3: OFF
To define the pump control settings.
BC
PUMPCONTROL
PUMPLEADTIME : 020s
PUMPLAGTIME : 000s
DAILY ON : Y AT : 00h00
To define the schedule timer.
BC
SCHEDULE TIMER
ENABLE TIMER : N
ENABLE HOLIDAY PER : N
BC
HOLIDAY : 01 TO 03
1 : 00h00 -
2: 00h00 -
3: 00h00 -
To define the dual evaporator pump.
BC
DUAL EVAP. PUMP
MODE : AUTOM. ROTATION
OFFSET ON RH : 0048h
To define the display settings.
BC
DISPLAY SETTINGS
LANGUAGE : ENGLISH
TIME : 00h00
DATE : 00/01/2001
To define whether or not a password
BC
SETPOINT PASSWORD
PASSWORD NEEDED TO
is needed to enter the setpoints
CHANGE SETPOINTS : Y
menu.
To enter the service menu. (Only a
BC ENTER SERVICE
qualified
PASSWORD : 0000
access this menu.)
Timers menu
To check the actual value of the
BX
GENERAL TIMERS
LOADUP : 000s - DWN : 000s
general software timers (first screen).
PUMPLEAD : 000s
FLOWSTOP : 00s
To check the actual value of the
BC
COMPRESSOR TIMERS
COMPR. STARTED : 00s
general software timers (second
screen).
To check the actual value of the
BC
COMPRESSOR TIMERS
C11 GRD : 000s AR : 000s
compressor timers (first screen).
C12 GRD : 000s AR : 000s
C21 GRD : 000s AR : 000s
installer
is
allowed
to
EWWQ049~064KAW1M + ECB2+3MUCW
Packaged water-cooled water chillers
D-EOMHP01008-17EU_01