11.2 Setting ranges for the switching outputs
Measurement
Lower limit of
range
RP / FL
in bar
in bar
0 .. 16
0.15
0 .. 25
0.25
0 .. 40
0.4
0 .. 100
1.0
0 .. 250
2.5
0 .. 400
4
0 .. 600
6
* All ranges shown in the table can be adjusted by the increments shown.
SP = switch point
RP = switch-back point
FL
= pressure window lower value
FH = pressure window upper value
Measurement
Lower limit of
range
RP / FL
in psi
in psi
0 .. 500
5
0 .. 1000
10
0 .. 3000
30
0 .. 6000
60
0 .. 9000
90
* All ranges shown in the table can be adjusted by the increments shown.
Edition: 2020-04-21
Upper limit
Minimum
of SP / FH
difference betw.
RP and SP
or FL and FH
in bar
16.00
0.15
25.00
0.25
40.0
0.4
100.0
1.0
250.0
2.5
400
4
600
6
Upper limit
Minimum
of SP / FH
difference betw.
RP and SP
or FL and FH
in psi
500
5
1000
10
3000
30
6000
60
9000
90
HYDAC ELECTRONIC GMBH
EDS 820 IO-Link
Increment*
in bar
0.05
0.05
0.1
0.2
0.5
1
1
Increment*
in psi
1
2
5
10
20
Part No.: 669916 E