EDS 820 IO-Link
10.2 Parameterisation in SIO mode
If IO-Link is not used, the EDS 820 IO-Link functions as a pressure switch with two
switching outputs.
It can be flexibly adapted to the relevant customer application in conjunction with the
HYDAC programming device HPG P1-000 or the programming adapter ZBE P1-000.
10.3 Parameterisation with HPG P1-000
(Connection via standard cable)
1
2
3
Device
4
5
10.4 Parameterisation with ZBE P1-000
(Connection via standard cable)
1
2
3
Device
4
5
11
Output settings
11.1 Switching outputs
The EDS 820 IO-Link has 2 switching outputs whose switching behaviour (window
mode or twopoint mode) is parameterisable.
NOTICE
If the sensor is operated at the Class-B port of an IO-Link master, pin 2 of the sensor
may not be connected to pin 2 of the master, as pin 2 of the master serves as a current
source for devices with increased power demand or for actors, which would collide
with the switching output of the EDS 820.
In addition to the IO-Link Smart Sensor Profile Specification, a switch and switch-back
delay can be set in HYDAC IO-Link sensors.
Edition: 2020-04-21
1
+Ub
2
3
0 V
HPG P1
Q1 / C
4
5
1
L+
Q2
2
3
L-
ZBE P1
Q1 / C
4
5
HYDAC ELECTRONIC GMBH
1
+Ub
2
3
0 V
4
USB
PC
11
Part No.: 669916 E