Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens CKA4820 Betriebsanleitung Seite 79

Bediengerät
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Siemens Building Technologies
Fire Safety & Security Products
Star network control
Up to 8 telemetry devices can be connected in a star network to the telemetry
interface COM2 using a TTY multiplexer.
The advantage of this mode is that only one telemetry device fails if there is a fault
in a control line following the TTY multiplexer. Disadvantage: many control lines
are required.
Outputs
1
TTY
multi-
plexer
8
Fig. 20
System with star network control
Required accessories
One TTY multiplexer (e.g. 8-channel TTY multiplexer, Order No.: 2GF5505-
8AK).
Control line: 2-core cable, max. permissible length approx. 1.2 km with 0.8 mm
conductor diameter
9-pin Sub-D plug with housing.
The power supply to the control unit is from a separate power supply unit.
Before connecting the telemetry devices, please refer to the information in the respective Instruction
Manuals.
TTY
DCU
TTY
CAC
0101
TTY
DCU
TTY
COM2
COM1B
SCU protocol
System Design
SIVIS MINI
DOME III
SICOLOR
DIG K505
SIVIS MINI
DOME III
12 V
200 mA
COM1A
Power
supply unit
79