8.7.31 Analog inputs (4.3.8.1 - 4.3.8.7)
Fig. 79 Analog inputs
Description
In the menu, you can set "Analog inputs". Each display is divided
into three parts:
Setting of input signal, for instance 4-20 mA
"Measured input value", for instance "Outlet pressure"
Measuring range of the sensor/signal transmitter, for instance
0-16 bar.
Setting range
You can set the following parameters in each display:
Not used
Range of input signal, 0-20 mA, 4-20 mA, 0-10 V
Measured input value
Sensor range.
Setting via the operating panel
Settings > Secondary functions > Stop function > Go to setting
of analog input.
If an analog input is deactivated, the display only
shows the top part, that is the setting of the analog
input.
If the input is activated, the middle part, "Measured
input value", is shown. This makes it possible to
relate a function to the analog input in another
display. When the analog input has been related to a
function, CU 352 will return to the display for setting
of analog inputs.
Factory setting
Pressure boosting
Analog input
Function
AI1 (CU 352) [51] Outlet pressure
Heating and cooling
Analog input
Function
AI1 (CU 352) [51] These are selected in the startup wizard
8.7.32 Analog inputs and measured value (4.3.8.1.1 -
4.3.8.7.1)
Fig. 80 Analog inputs and measured value
Description
A function can be related to the individual analog inputs.
Setting range
You can select one function per analog input. For further details,
see the installation and operating instructions for Control MPC.
Not used
0-100 % signal
Inlet pressure
Outlet pressure
External pressure
Diff. pressure, pump
Flow rate 1-3
Tank level, outlet side
Tank level, suction side
System pressure
Diff. pressure, external
Tank precharge pressure
Diff. pressure, inlet
Diff. pressure, outlet
Return-pipe temp., external
Flow-pipe temperature
Return-pipe temperature
Differential temperature
Ambient temperature
Power, pump 1-6
Power, VFD
Multisensor 1-6.
Setting via the operating panel
If more flow rates are used, the flow rate measured
and shown is the sum of defined flow rates.
Settings > Secondary functions > Go to setting of analog input.
1. Select analog input.
2. Select: Measured input value. Display 4.3.8.1.1 appears.
3. Select input.
4. Press [Back].
5. Set the minimum and maximum sensor value.
49