UK: VACON
3. Cable requirements
The following table shows the maximum sizes for the cables to be used with the drive supply switch.
NOTE! Use only copper cables with the drive supply switch option, no aluminium cables allowed!
Frame
MR4
MR5
MR6
MR7
* Cables with heat resistance of at least +90°C must be used.
4. Mechanical dimensions
Drive size
MR4
MR5
MR6
MR7
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Downloaded from
www.Manualslib.com
®
100 drive supply switch
Table 1. Cable data for the drive supply switch option
Maximum mains
Type
and motor cable
0003 2 - 0004 2
0006 2 - 0008 2
0011 2 - 0012 2
0003 5 - 0004 5
0005 5 - 0008 5
0009 5 - 0012 5
0018 2
0024 2
0031 2
0016 5
0023 5
0031 5
0048 2
0062 2
0038 5
0046 5
0061 5
0075 2
0088 2
0105 2
0072 5
0087 5
0105 5
Table 2. Mechanical dimensions of the drives with drive supply switch option
Width (mm)
128
144
195
237
manuals search engine
Tightening torque of
the drive supply
2
size (mm
)
switch screws (Nm)
3 x 1.5 + 1.5
3 x 1.5 + 1.5
3 x 2.5 + 2.5
3 x 1.5 + 1.5
3 x 1.5 + 1.5
3 x 2.5 + 2.5
3 x 6 + 6
3 x 6 + 6
3 x 10 + 10
3 x 6 + 6
3 x 6 + 6
3 x 10 + 10
3 x 16 + 16
3 x 25 + 16
3 x 10 + 10
3 x 16 + 16
3 x 25 + 16
3 x 35 + 16
3 x 35 + 16
3 x 50 + 25*
3 x 35 + 16
3 x 35 + 16
3 x 50 + 25*
Height (mm)
Depth (mm)
328
419
557
660
vacon • 7
Insulation tube size
for supply cable,
diameter/length (mm)
0.8
10/70
0.8
16/80
2
20/80
6
25/80
Weight (kg)
270
6.5
295
10.5
302
20.5
332
38.5
uk