Mounting / dismounting, operating position
This device is suitable for outdoor and indoor use.
• Provide a protective roof or wall if enclosure and explosion protected electrical
• For the operating position refer to the attached documentation.
• Mount the component on a flat surface.
• Fasten the device to the mounting holes, provided for this purpose, using suitable
• Place the Ex d enclosure on the mounting rail and connect it using M12 screws
167225 / 8264605300
2015-02-03·BA00·III·en·04
Downloaded from
www.Manualslib.com
Ex e terminal compartment.
To prevent condensation in the enclosure, we recommend using a breather,
type 8162 by R. STAHL Schaltgeräte GmbH.
By using a breather and depending on its mounting position, the degree of
protection acc. to IEC 60529 is reduced. If mounted lateral, the degree of
protection is IP64, if opening of breather is installed downwards, it is IP56.
Explosion hazard due to unauthorized cable entries!
Non-compliance results in severe or fatal injuries.
• Use only cable entries approved for the required type of protection.
• When selecting cable glands, observe the thread type and thread size
in the equipment documentation.
Explosion hazard due to open holes or unused cable glands!
Non-compliance results in severe or fatal injuries.
• Always close drilled holes and unused cable glands using approved
stopping plugs or plugs.
• When selecting cable glands, observe the thread type and thread size
in the equipment documentation.
Mechanical overload of the device!
Non-compliance can result in severe or fatal injuries and material damage.
• Install protective wire grid.
• Install the device only in locations with little vehicle and pedestrian
traffic.
equipment is used outdoors.
screws and accessories (see dimensional drawings).
(observe weight, see chapter "Technical data")
manuals search engine
Mounting and installation