Arrangement and fitting

6.1 Dimensions

6.2 Installation

The isolating repeater may be installed in Zone 2, Zone 22 or outside hazardous areas.
In the case of operation in Zone 2 or Zone 22, the isolating repeater must be fitted in an
enclosure which complies with the requirements of EN 60079-15 or EN 61241-1 (e.g. in an
enclosure type 8146 from the R. STAHL Schaltgeräte GmbH company).

6.3 Mounting and dismounting

a) Detachable terminals
All devices are provided with detachable terminals. A screwdriver is
needed to remove the terminals (as shown in the picture).
b) Mounting on DIN rails
Set the device on the DIN rail and tilt/snap onto the rail as depicted.
Do not set at an angle. For removal, pull the base latch out a little
with a screwdriver and remove the module.
c) Mounting on DIN rails with an already-installed pac-Bus
As depicted in the photo, set the device in position on the pac-Bus (already mounted on the
DIN rail) and tilt/snap until it locks in.
Do not tilt at an angle to either side when snapping onto the pac-Bus.
Note: In order to prevent pole reversal during installation, the pac-Bus
elements have been equipped with a keyed connection plug (see photo).
The module is fitted with a matching slot.
Dismount as described below in b).
14
Isolating Repeater Output Type 9165 Rev. C
Screw terminals
Spring clamp terminals
english
Size X
108 mm
128 mm