Internal wiring

For instance, the following types are suitable for the temperature classes listed below:
Type
H 05 G-K
H 07 V-K
H 05 V-K
LIY
H 07 NSGAFÖU
or similar types
Distances, creepage distances and clearances
• The creepage distances and clearances between the individual components as well
• The creepage distances between the components must be tested and observed
• At least the required clearance, which is the minimum distance between cover and
Insulation test voltage
As regards insulation and separation of terminals and conductors observe the following:
• Insulation test voltage is calculated from the sum of the rated operational voltages of
"Intrinsically safe against earth"
In case of "intrinsically safe to earth", there is a minimum insulation voltage value of 500
V (otherwise, double value of the rated operational voltage of intrinsically safe circuits).
"Intrinsically safe against non-intrinsically safe"
In case of "intrinsically safe against non-intrinsically safe" the insulation voltage value is
at least 1500 V (otherwise, doubled sum of the rated operational voltage of
intrinsically-safe circuits plus 1000 V).
167225 / 8264605300
2015-02-03·BA00·III·en·04
Downloaded from
www.Manualslib.com
Explosion hazard due to incorrectly routed and damaged conductors!
Non-compliance results in severe or fatal injuries.
• Lay the conductors in such a way that damage
(e.g. due to bending, fraying) during operation is avoided.
• Adhere to the required creepage distances and clearances.
For the internal wiring use only conductors suitable for the operating
temperature range!
Temperature class Conductor cross-
T5
T6
T6
T6
T5
as between the components and the enclosure walls must be dimensioned sufficiently.
according to the specifications of the relevant operating instructions.
connection screw of the build-in components (with the conductor connected) must be
observed for all control panels.
intrinsically safe and non-intrinsically safe circuits.
manuals search engine
DANGER
section
2
)0.5 mm
, Cu
Control and Distribution Panel in
flameproof enclosure
Mounting and installation
19