Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - WIKA BGU-...D serie Betriebsanleitung

Bypass-magnetschalter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

9

Technical data

9.1 Electrical data for Ex d devices
Switch
BGU-...D
Type
BGU-...D
BGU-...RD
BGU-...ND
BGU-AMD
BGU-AMRD
BGU-AMND
54
Approval
II 2G Ex db IIC T6...T1 Gb
II 2 D Ex tb IIIC T80°C...145°C Db
Switching element
Ex d
Reed contact
Ex d
Reed contact
with series resistor
22 Ohm
Ex d
Reed contact
with equivalent cir-
cuit in accordance
with EN 60947-5-6
(NAMUR)
Ex d
Microswitch
Ex d
Microswitch
with series resistor
22 Ohm
Ex d
Microswitch
with equivalent cir-
cuit in accordance
with EN 60947-5-6
(NAMUR)
KSR KUEBLER Operating instructions Bypass magnetic switch - BGU-...D
Switching capacity
AC ≤ 230V; ≤ 2A
DC ≤ 230V; ≤ 2A
AC ≤ 230V; ≤ 100mA; ≤ 1 VA
DC ≤ 230V; ≤ 100mA, ≤1 W
AC ≤ 18,5V; ≤ 30mA, ≤ 0,4 VA
DC ≤ 18,5V; ≤ 30mA, ≤ 0,4W
AC ≤ 250V; ≤ 5A
DC ≤ 250V; ≤ 5A
AC ≤ 230V; ≤ 100mA; ≤ 1 VA
DC ≤ 230V; ≤ 100mA, ≤1 W
AC ≤ 18,5V; ≤ 30mA, ≤ 0,4 VA
DC ≤ 18,5V; ≤ 30mA, ≤ 0,4W