P901 Memory Test
Press ENTER
Values (view only)

Measurement

P911 mA Output Value
Access this parameter to display the current value of the mA output.
Values (
HART)
1. Set P201 to 0 (manual).
2. Enter a test value.
Note:
P201 must be set to 0 to enable the test value to be entered at P911: be sure to
restore P201 to the previous setting after the test!
P912 Temperature
Displays the temperature in
not affected by Temperature Source (P660).
Values (view only)
7ML19985HT01
to activate the test.
IdLE
Normal operation
PASS
Memory test successful
F1
Fail RAM
F2
Fail EEPROM
F3
Fail FLASH
Range
Default
o
C (as monitored by the connected transducer). This value is
Range
SITRANS Probe LU – INSTRUCTION MANUAL
3.6 to 22.6 (mA)
4 mA in HART fixed current mode
o
–40 to 85 (
C)
Page 61