The configurable value corresponds to the value starting at which you consider the cold to not be satisfactory for your use, if this is exceeded
for more than 10 mn, this fault will automatically be displayed on the screen and recorded for later viewing.
Setting the pre-programmed values for reheating duration : this screen allows you to set the values in the following way :
y Recording :
This traceability module provides access to the following functionality :
Fault recording
Fault recording :
Cold fault
Power fault
Cold fault : this module allows a cold fault to be tripped if the fault temperature set by the manager (9° by default) is exceeded for more than
10 mn. No fault is recorded as long as the cold temperature setting is not reached.
These faults are then stored and can be consulted in the screen below :
Core temperature retherm fault : this module allows a fault to be tripped if the core temperature read by the insertion sensor is not reached
within 1 hour in accordance with current regulations.
These faults are then stored and can be consulted in the screen below :
Recording button
Reheating graph
Data extraction
Core temperature reheating fault
Reheating door open fault