MICROPROCESSOR CONTROL UNIT FOR SLIDING GATES 400V
USER INSTRUCTIONS - INSTALLATION STANDARDS
Thanks to the high-power performance of its built-in microprocessor, this control unit for sliding gates with three-phased 400V
motor offers a wide number of services and adjustments.
The main settings and operating modes can be defined using dip-switches while time adjustments are performed using the
trimmers installed on the electronic circuit board.
7 built-in LEDS constantly display the status of inputs, outputs in addition to any circuit malfunctions.
Power supply
Absorbed power
Max. motor load
Max. load on accessoies
Ambient temperature
Protection fuses
Operating logic
Opening /closing time
Pause time
Partial opening time
Terminal board inputs
Radio control connector
Terminal board outputs
Functions selected with dip-switches
Housing dimensions
Housing degree of protection
3. TERMINAL BOARD M1 M2(HIGH VOLTAGE) CONNECTIONS - DESCRIPTION
3.1 400V POWER SUPPLY
Terminals "1 - 2 - 3" . Connection to power supply network 400V~ 50/60 Hz.
3.2 GEAR UNIT
Terminals "4 - 5 - 6" Connect the three-phased motor to terminals T1 - T2 - T3 or T1 - T3 - T2 according to the installation (on the
right or left hand) of the gear motor onto the gate.
WARNING: The gear motor is in the right-hand version in the wiring already provided for.
4. TERMINAL BOARD M3 (HIGH VOLTAGE) CONNECTIONS - DESCRIPTION
4.1 FLASHER
Terminals "7 - 8" (Phase - Neutral). Use a flasher with an operating voltage of 230 V~(100W. max.). When power is supplied to
the system the flasher will blink to confirm that the unit is properly connected to the electric power supply.
4.2 230V POWER SUPPLY
Terminals "9 - 10" (Phase - Neutral). Connection to 230V~ 50/60 Hz power supply network.
Notes:
1)
To install sheaths andelectric cables, use adequate separate rigid and/or flexible tubes to avoid interferences.
2)
Always separate the low-voltage accessory connection cables from the 230V~ or 400V~ power supply cables.
Two magnetothermal switches with adequate tripping threshold should be provided for upstream of the equipment
5. TERMINAL BOARD M4 (LOW VOLTAGE) CONNECTIONS - DESCRIPTION
5.1 GATE STATUS LED
Terminals "12-13". The signal led constantly displays gate status and motion. OFF = gate closed; ON = gate open; SLOW FLASHING
= gate opening; FAST FLASHING = gate closing.
5.2 STOP
Terminals "14-15" (Circuit Normally Closed). The status of this input is signalled by LED 2. This circuit is connected to any device
(e.g. button, pressure switch) which, when a contact is opened, can stop the gate motion. It can be used as a safety device
on the opening motion.
Note: If STOP devices are not connected, jumper connect the input. To install multiple STOP devices, connect the NC contacts
in series.
1. GENERAL FEATURES
2. TECHNICAL FEATURES
Automatic with stop / Step-step with stop
Adjustable using trimmer (from 12 to 120 sec.)
Adjustable using trimmer (from 0 to 120 sec.)
Closing photocells / Opening-closing limit switch /
Accessory power supply 24 V~ / Flasher /
5
400/230 V~ (+6 -10%) - 50/60 Hz.
10 W
2KW
500 mA
-20°C +50°C
3
Automatic / Semi-automatic /
Fixed 10 sec.
Total opening / Partial opening /
STOP / Mains power supply 400/230 V~
Radio receiver boards molex connector
Gate status led / Motor
Operating modes
Closing photocell reaction
90 x 195 x 250 mm.
IP54
ENGLISH